BACER Installation and Initial Testing

Written by CIM Support

Testing the BACER Configuration

Internet Access

With a laptop, using the same IP settings as the BACER, connect into the assigned installation location and test to see if the internet connection is live. e.g. 10.137.30.6, subnet 255.255.255.0 (How to set a static IP in Windows)

Specifically test if https://vpn.cimenviro.com is reachable and should show the below screen:

If this loads, the BACER should be able to connect to the CIM VPN.

BACnet Visibility

Once connected and internet access is confirmed, next BACnet visibility should be tested. This is done via a BACnet scanner, such as YABE. Instructions for YABE are below

  1. Connect your laptop in place of the BACER and run a scan on YABE

    • Click green + in the top left

    • Under BACnet/IP over UDP, select your IP from local endpoint dropdown list (10.137.30.6) and click add

    • Devices should appear automatically.

  2. If devices appear, this indicates that our BACER will see those devices. If not, then further troubleshooting required

Physical Installation

  1. Connect the ethernet on both ends

  2. Connect power to BACER. BACER should turn on automatically. It will likely take a few (~3-5?) minutes to finish booting and connecting to the CIM servers.

  3. Once connected, it should update the "Last Poll" timestamp in PEAK, under Site Manager>BACER>siteName.

  4. If issues, reach out to your CIM contact