Generating Points Lists on WebCtrl or iVu Systems

Written by CIM Support

Automated Logic / Carrier / Systemax / WebCtrl

Points List

This BMS is able to generate points list reports, which allow us to start with commissioning and audit sheets prior to installing BACERs. Steps below:

  1. Select site as highest item in navigation tree. This ensures report runs over the entire site

  2. Select points list report as per below screenshot

  3. Ensure from the report options:

    1. Max rows is sufficient (i.e. 100,000 rows)

    2. Minimal columns (value, object/device ID + object name, path recommended)

    3. Include BACnet points only. Make 2 reports initially

Two lists should be generated on initial onboarding phase - one with “Network Visible” ticked, and one without. Network visible indicates points we can commission immediately, whereas the other will also provide points we can commission after some effort to tick some “Network Visible” boxes on the specified points. It is good practice to keep a copy of both in case we need to revert to original settings if issues arise.