Skip to main content

General Commissioning Tips

Things to keep in mind when commissioning

CIM Support avatar
Written by CIM Support
Updated yesterday

Common Equipment

Don’t use Building → use Common AHU

Ensure points are shared correctly, this may mean the creation of several shared equipment to cover various combinations. E.g. AHU 1 and 2 may share a return duct, but AHU 1, 2, and 3 may share an outside air plenum so two common equipment should be made:

Common AHU 1 and 2 for the return duct points, Common AHU 1 2 and 3 for the outside air points.

Inputs and Outputs Vs Values

Inputs / outputs represent the actual signals going into and out of the controllers. These are essentially the ‘raw’ values and should always be used where possible.

This only applies if there are duplicate points that represent the same metadata have the same value

Important Metadata

Chillers

Critical:

  • Chilled water entering Temperature

  • Chilled Water leaving Temperature

  • Chiller Enable

  • Chiller Fault

  • Chiller Status

  • Condenser Water Entering Temp

  • Condenser Water Leaving Temp

  • Evaporator Pressure

  • Evaporator Pressure setpoint

  • Condenser Pressure

  • Condenser Pressure setpoint

  • Chiller Power Consumption - HLI

  • Chiller Power - HLI

  • Chiller Run Amps - HLI

  • COP - (where available)

  • Cooling/Thermal Load (Where available)

VSD

Critical:

  • Operating Frequency

  • Power

  • Energy Consumption

If available:

  • Status

  • Enable

  • Power Factor

  • Torque

  • Hand / Auto

  • Current

  • Speed

Power Meters

Critical:

  • Power

  • Energy Consumption

HLI Differences

High Level Interfaces (HLIs), which include VSDs, represent devices that receive low level inputs from the BMS to inform their own internal controls and produce the desired output. These devices will allow certain points to be read and can act either as feedback to the BMS or other monitoring purposes. E.g. BMS will tell a Chiller it wants 6 degree water. The Chiller internal controls will calculate and action how it will achieve this. The HLI will allow the BMS to read specific points to determine if this is what it wants from the system as a whole, such as COP, capacity, etc.

Typically we will want those points on their own devices rather than their parent equipment, following the naming convention for that particular equipment.

Power sub-meters also will have similar naming conventions on a BMS, containing many similar points that we are interested in. e.g. power and energy consumption.

To determine which is which:

  • Look at how many equipment are referenced on the device (more than 1 indicates a power sub-meter)

  • Look at points available (e.g. active power or energy consumption indicates one of these three but additional points such as pressures of speeds will rule out power sub-meters)

  • Device model and vendor

    • ABB, Danfoss, are VSD manufacturers

    • Carel, York, Mcquay, Carrier are Chiller manufacturers (Chiller HLIs)

    • NEMO are PSMs

  • If in doubt, prioritise PSM over VSD and HLI if only power and energy can be found

BMS Meters

Required to check on BMS to confirm what type of aggregation has been configured (e.g. do they reset at specific intervals like each day, or are they cumulative). Where possible, total cumulative usage is preferred over a usage that resets over a set period of time (daily, monthly etc)

Car Park Ventilation

CO sensor questions - how to zone, how to allocate

Typically CO sensors will go on a common equipment (e.g. Common Car Park Basement 1), with a zone based on the CO sensor number (CO sensor 1 is Level: Basement 1, Zone: 01). Car Park Exhaust and Supply Fans would then have their own equipment, and have the common equipment shared to them as per standard practice. Common equipment should but created as required (e.g. common to the floor, or if further subdivided by east and west etc, additional common equipment should be created).

No BMS Access

Concerns for lack of BMS access and minimising rework:

  • Which point links with which
    Best guess, can rename equipment, level and zone later. Important to get data in within a timely manner where there is an option to rename simple things later.
    e.g. If VSDs are not well defined, commission them with their device name and rename the equipment when more information is gathered. This is less advisable for units requiring specific level and zones like VAVs as there is currently no simple way to convert all favourites to a specific level and zone.

  • What to do with duplicates
    Consider manually commissioning both for 1 equipment and compare the trends after a significant period. This is also useful for input/output vs value

  • How to do parent-child mapping
    Base it on FD or other documentation.

Did this answer your question?